3VA2010-6JQ32-0AE0

circuit breaker 3VA2 IEC frame 100 breaking capacity class H Icu=85kA @ 415V 3-pole, line protection ETU560, LSIG, In=100A overload protection Ir=40A…100A short-circuit protection Isd=0.6..10x In, Ii=1.5..12x In N conductor protection optionally with external current transformer, up to 160% gr.-fault prot., can be sw. off Ig=0.2…1 x In, tg=0.05-0.8s nut keeper kit 4 auxiliary switches HQ

SKU: 3VA2010-6JQ32-0AE0 Category:

Description

Siemens | 3VA2010-6JQ32-0AE0 | circuit breaker 3VA2 IEC frame 100 breaking capacity class H Icu=85kA @ 415V 3-pole, line protection ETU560, LSIG, In=100A overload protection Ir=40A…100A short-circuit protection Isd=0.6..10x In, Ii=1.5..12x In N conductor protection optionally with external current transformer, up to 160% gr.-fault prot., can be sw. off Ig=0.2…1 x In, tg=0.05-0.8s nut keeper kit 4 auxiliary switches HQ